Preparing details for thermal analysis.

To verify envelope performance for Passive House certification, BLDGTYP runs thermal simulations of your typical assemblies and critical junctions. Those models depend on clean CAD base-files from the design team. This guide covers what to draw, how much to include, and how to format the files so the models come out right on the first pass.

Three-step thermal simulation workflow: a flat 2D CAD base-file, closed polygons with materials assigned, and the finished heat-transfer simulation
1) Draw a flat 2D CAD base-file for each assembly and detail at full scale, with hatches, notes, and dimensions removed to leave clean outlines.  2) In the simulation software, we build closed polygons for every element, assign material properties (conductivity, emissivity, etc.), and set interior and exterior boundary conditions.  3) We run the simulations and pull R-values and surface temperatures for the whole-building model or certification submittal.

Why we need base-files.

For Passive House certification, BLDGTYP runs thermal simulations of all typical building assemblies (walls, roofs, and floors) and all thermal bridges at junctions between envelope elements, such as roof-to-wall intersections.

Your team prepares flat 2D CAD base-files and sends them to us. We import those drawings into our simulation software to calculate:

  • R-values of all assemblies
  • Psi-values of all critical junctions
  • Minimum interior surface temperatures for moisture and mold durability

// Reference standards: all thermal-bridge models follow ISO 10211 ("Thermal bridges in building construction"), ISO 13788 ("Hygrothermal performance of building components and building elements"), and ISO 10077-2 ("Thermal performance of windows, doors and shutters").

Pages from a project thermal-bridge catalog, collecting each envelope detail alongside its simulation results
A project detail catalog pairs each envelope detail with its thermal-analysis results for certification review.

Every detail goes into the catalog.

As part of the Passive House certification submittal, BLDGTYP puts together a detail catalog that pairs every key architectural detail with its simulation results. Certifiers rely on this catalog during review.

We need accurate geometry, material callouts, and any special field notes from the design team so the catalog stays consistent with the architectural set and the whole-building energy model.

Every detail in the catalog needs to match as-built conditions as closely as possible.

An architectural floor-connection detail showing insulation, air barrier, vapor control, and structural bridging elements clearly labeled
A drawing-set detail should clearly label insulation layers, structural and bridging elements, air-tightness, vapor control, and waterproofing.

What each detail must show.

Document each detail and assembly in the architectural drawing set so the catalog can reference it, usually as its own detail drawing. For Passive House review, every detail should clearly show:

  1. All insulation layers and materials in the envelope.
  2. All structural and bridging elements penetrating the insulation, such as studs, beams, or shelf angles, with their material callouts or product names.
  3. All air-tightness layers and materials.
  4. All moisture and vapor-control layers and materials.
  5. All exterior waterproofing.
CAD drawing of thermal-bridge details being prepared: flat linework organized on layers, with a thumbnail index of the detail set
Deliver base-files flat, full-scale, in DXF or DWG, with all objects drawn as closed polygons.

How to prepare the CAD.

Draw at full scale and export as DXF or DWG. Keep the file completely flat with no 3D elements, and remove hatches, dimensions, and notes or move them onto separate layers away from the geometry profiles. Explode groups, blocks, and dynamic objects down to raw, flat linework. Draw every simulated object as a closed polygon with coincident vertices and no gaps or breaks in the lines.

You can put multiple details or assemblies in a single CAD file as long as they don't touch or overlap and the layout is easy to follow.

If you want to leave notes or detail labels for the thermal modeler, put them on the "Defpoints" layer.

Diagram of a 2D corner junction showing minimum drawing length equal to the larger of 3x the assembly thickness or 1m, plus half a stud bay, with a right and wrong example of closed polygons
Minimum dimension (d) = larger of 3×b or 1m in each direction. Extend past the minimum to include half a typical stud/joist bay (Lw). Right: vertices coincident with no gaps.

How much to draw at a junction.

Under ISO 10211, corners, parapets, and other junctions need a minimum length (d) of 1m in both x and y directions. Length (d) must also be at least 3× the assembly thickness (b). If the assembly has repeating framing such as studs or joists, extend past that minimum to include half a typical bay (Lw). Drawing larger than the minimum is fine.

What if the actual wall is shorter than 1m? Even if a window or door sits closer than 1m to the corner, leave it out of this detail. Draw only the typical assembly and the structural elements (columns, beams) tied to the corner or intersection being modeled. Disruptions like window jack studs get modeled separately and entered into the energy model as their own thermal bridges.

Keep every simulated element as a closed polygon with touching or overlapping vertices and zero gaps.

Diagrams of a framed assembly with two repeating studs and an unframed assembly showing a 32-inch minimum drawing length
Framed assembly: include at least two typical framing members plus half-bays. Unframed assembly (e.g. cast-in-place slab): draw a minimum of 32″ long.

How much to draw for R-value.

We simulate the effective R-value of each typical assembly, including all material layers, framing members, finish surfaces, battens, and air layers.

For framed walls, floors, and roofs, draw the section long enough to show at least two typical framing members such as studs or joists. For unframed assemblies like a cast-in-place concrete slab, draw at least 32″ of length.

Where thermal bridges hide.

Plan to draw and simulate any location where the envelope turns more than 60°, where the primary insulation changes thickness, or where bridging elements or material changes alter the insulation's conductivity. If you're not sure whether a detail needs modeling, send it over and we'll check it together.

A grid of common junction thermal-bridge detail types: parapets, balconies, floor-to-wall connections, footings, roof mountings, beam bearings, penetrations, overhangs, eaves, canopies, and elevator pits
Common junction details required for thermal-bridge analysis.
  • AAll parapet details, including any mountings for railings or guardrails.
  • BAll balcony details, including thermal-break products with correct dimensions / thicknesses.
  • CAll floor-to-wall connections, particularly where "interior" insulation is used.
  • DAll footings / walls below grade and floor-to-wall connections; indicate average grade level relative to floor.
  • EAll roof mountings / footings for elements such as HVAC, solar, or other fixed objects.
  • FAll details bearing on steel or concrete beams, particularly at roof decks.
  • GAll penetrations through the wall or roof, including HVAC, plumbing (roof drains), and electrical.
  • HAll footings or floor-to-wall connections at grade; indicate average grade level relative to floor.
  • IAll roof overhangs, eaves, or cornices.
  • JAll overhangs / bays that protrude from the main geometry, including all floor insulation layers.
  • KAll connections for canopies, signs, awnings, fire escapes, or other exterior elements that anchor through the insulation.
  • LAll elevator-pit details, including any raft-slab / footings and vertical walls up to floor level.
Finite-element thermal simulations of a window jamb, head, and sill showing temperature gradients and surface-temperature factors through the frame and surrounding assembly
Windows need head, sill, and jamb base-files per unique type, drawn with all blocking, framing, and trim insulation out to 1m from the frame.

A special case.

Windows and doors need more detail than standard wall junctions. Provide separate head, sill, and jamb base-files for each unique window type. A unit with more than one frame profile, such as a simulated double-hung with two different jambs, may need extra details. Include all exterior doors too, especially thresholds, which are a common spot for condensation risk.

If the same window frame is installed two different ways or sits in two different wall assemblies, give each condition its own base-files.

Include all blocking, framing, trim insulation, and installation components. Draw the actual frame profile accurately, keeping in mind that sills and jambs often differ from heads, especially on doors and sliders. When a window or door meets more than one assembly (such as a roof deck), extend those assemblies using the same minimum dimensions above (at least 1m and 3× thickness).

Have details that need thermal-bridge modeling?

Send your detail set and we'll tell you which junctions need simulation and how to prep the base-files. See our thermal-bridge modeling and NYC 2025 energy-code pages for more.